We specify materials carrying at least one of these listings and design every system to the codes below. Civil Defense approval is the final check, and our documentation is prepared for it from day one.

UL Listed, FM Approved, LPCB, VdS, NFPA
Design codes

The codes we design to

NFPA 13

Sprinkler installation

NFPA 14

Standpipe & hose

NFPA 20

Fire pumps

NFPA 24

Private fire mains

NFPA 25

Inspection & maintenance

NFPA 2001

Clean agent systems

NFPA 12

CO₂ systems

NFPA 10

Portable extinguishers

NFPA 72

Fire alarm interface

EFC

الكود المصري لحماية المنشآت من الحريق

Where the Egyptian Fire Code and NFPA differ, we design to the stricter requirement and note it on the drawings.

Testing before handover

Every system is proven

TestCriteriaReference
Hydrostatic test200 psi (13.8 bar) for 2 hours, no pressure lossNFPA 13
Underground flushingMains flushed before connection to risersNFPA 24
Main drain testStatic and residual pressure at each riserNFPA 25
Alarm valve tripFlow switch, gong and panel signal per zoneNFPA 13
Pump acceptance0%, 100% and 150% of rated flowNFPA 20
Room integrityDoor-fan test to confirm agent hold timeNFPA 2001
Handover package
✓ Material submittals✓ Signed test certificates✓ As-built drawings✓ O&M manuals✓ Operator training✓ Civil Defense file